Selecting essentials of modules |
(1) Silicon photovoltaic module:2.4 m (L) x 1.25 m(W) or less
(2) Must qualify all safety, performance, efficiency and reliability |
|
|
|
PV Module Assessment Items:
Category |
Reference standard |
Requirement content |
Pass criteria |
Safety |
IEC 61730-2: 2004 or CNS 15118-2: 2007 or above |
Safety test |
Meet the reference standard |
Performance |
IEC 61215: 2005 or CNS 15114: 2007 or above |
Performance test |
Meet the reference standard |
Efficiency |
IEC 60904-1:2006 |
STC max. power test, calculating efficiency according to external frame area of module |
efficiency ≧ 20.0 % |
Reliability
(Salt mist corrosion test) |
IEC 61701: 2022 Severity 8 |
70 Days |
6 items are qualified |
Power degradation ≦ 5 % |
Reliability
(Damp heat test)
|
IEC 61215:2005 or CNS 15114: 2007 or above |
DH 3000
|
4 items are qualified |
Power degradation ≦ 15 % |
Reliability
(Thermal cycling test)
|
IEC 61215: 2005 or CNS 15114: 2007 or above |
TC 600 |
3 items are qualified |
Power degradation ≦ 15 % |
Reliability
(Potential Induced Degradation test, PID) |
IEC TS 62804-1 : 2015 |
PID 85 °C , 85 %RH
± System Voltage 300 h |
4 items are qualified |
Power degradation ≦ 5 % |
Reliability
(Combination testing)
|
IEC TS 62782 : 2016 |
DML(±2500 Pa)-TC50-HF10 |
4 items are qualified |
Power degradation ≦ 5 % (single item)
Power degradation ≦ 8 % (all series) |
|
|
Selecting essentials of cells |
(1) Silicon solar cell: :166 mm x 166 mm or less
(2) Must qualify efficiency and reliability |
|
|
Category |
Reference standard |
Requirement content |
Pass criteria |
Efficiency |
IEC 60904-1:2006 |
Efficiency performance after exposure of 20 kWh·m-2 |
Efficiency ≧ 21.2 % |
Reliability
(Potential Induced Degradation test, PID) |
IEC TS 62804-1 : 2015 |
PID 85 °C 85 %RH
±System Voltage 192 h |
Power degradation ≦ 5 % |
Reliability
(Light and elevated
Temperature Induced
Degradation, LETID) |
IEC TS 63342 (Draft) |
LETID 75 °C, 85%RH;
I= (Isc-Impp)×2, 486 h |
Power degradation ≦ 5 % |
|
|
|
Selecting essentials of inerter |
(1) PV-Inverter:125 kW or less
(2) Must qualify all safety, performance, efficiency and reliability |
|
|
Category |
Reference standard |
Requirement content |
Pass criteria |
Safety |
CNS 15426-1: 2011、CNS15426-2: 2013 |
Safety test |
Meet the reference standard |
Grid-connected |
CNS 15382: 2018 |
Grid-connected test |
Meet the reference standard |
Electromagnetic Compatibility (EMC) |
CNS 14674-1~3: 2006、CNS 14674-4: 2016 or IEC 62920: 2017 |
EMC test |
Meet the reference standard |
Reliability
(Copper Accelerat-ed Salt Spray Test, CASS) |
ASTM B368-09 |
Mix 5 % concentration NaCl with CuCl2-H2O and glacial acetic acid , the pH value is between 3.1~3.3. Temp.: 49 ± 1 °C Time : 14 days |
Where applicable, the continuous output current or power shall not exceed 10% of the marked output rating value |
Reliability
(Thermal cycling test) |
IEC 61215: 2005 or CNS 15114: 2007or above |
Temp.: (-40 ~ 85) ± 2 °C Time : 200 cycles |
Where applicable, the continuous output current or power shall not exceed 10 % of the marked output rating value |
|
|
|
|
|